This article contains the steps to configure the Output.
Applies To:
XP-SNET 3.48 and above , XP-CPROA
Software xPortalNet
Resolution Summary
To configure the Output:
Connect the Output at the correct relays number from the controller board.
Then configure the Alarm Controller and Output Point.
After completed the configuration, download the Door Settings to the controller.
Resolution
Perform steps below to setup the Output.
Connect the output at the correct relays number. There are 8 relays reserved for the Output on the board.
If settings configured is for (Door Access + Alarm Mode), please refer table below for output configurations.
Field
Description
Output Relay 1 - 5
Output for Door, which can connect to EM Lock.
Only can be triggered by IN1 - IN10 (Door Sensor and Push Button)
Output Relay 6 - 8
Extra output relay.
Only can be triggered by IN11 - IN16 (Extra Input)
If settings configured is for (Alarm Mode), please refer table below for output configurations.
Field
Description
Output Relay 1 - 8
Only can be triggered by Sensor Input IN1 - IN16
Please ensure the controller is already configured and the status is "Up" before proceed.
Alarm Controller Setup
Login to xPortalNet Server.
Open Alarm Controller Setup. Go to Server Admin › System Device Setup › Alarm Controller.
Add one alarm controller.
Please select the correct Model No according to the installed alarm controller. If not connected to any alarm controller, set the Model No to Built-In IO.
Click OK to confirm and save settings.
Output Point Setup
Open Output Point. Go to Server Admin › System Device Setup › Output Point.
Add output point according to the connected output at the controller board.
Field
Description
Code and Description
Fill in the Code and Description
Alarm Controller
Select Alarm Controller
Point No
Set the Output Point - Which relay (RLY) the output is connected to.
Example: If Output is connected to RLY2, set the Point No to 1.