How to configure Input?
Author: Microengine Views: 15780 Created: 05-11-2015 11:23 AM 0 Rating/ Voters

This article contains the steps to configure the Input.

Applies To:

  • XP-SNET 3.48 and above, XP-CPROA    
  • Software xPortalNet
 Resolution Summary
 

To configure the Input:

  1. Connect the Input at the correct Input relay from the controller board.
  2. Then configure the Alarm Controller and Input Point.
  3. After completed the configuration, download the Door Settings to the controller.
 Resolution
 

Perform steps below to setup Input.


  1. Please connect the input at the correct Input number. There are 16 Input point reserved for the Inputs on the board.
    FieldDescription

    Door Access + Alarm Mode
    • Set DIP Switch setting 2 & 3 to ON.
    • Sensor IN11 - IN16 must connected with resistor 3k3 in supervised input mode.

    Alarm Mode
    • Set DIP Switch setting 3 to ON.
    • All sensor input point must connected with resistor 3k3 in supervised input mode.


  2. If settings configured is for (Door Access + Alarm Mode), please refer table below for input configurations.

    FieldDescription

    IN1 - IN10
    • For Door Input (Door Sensor and Push Button)
    • Only can trigger Output Relay 1 - Relay 5 (EM Lock Output)

    IN11 - IN16
    • For Sensor Input (Extra Input)
    • Only can trigger Output Relay 6 - Relay 8 (Extra Output)

  3. If settings configured is for (Alarm Mode), please refer table below for input configurations.
    FieldDescription

    IN1 - IN16
    • Sensor Input. Can trigger all Output Relay (1 - 8)
Please ensure the controller is already configured and the status is "Up" before proceed.

Alarm Controller Setup


  1. Login to xPortalNet Server.
  2. Open Alarm Controller Setup. Go to Server Admin › System Device Setup › Alarm Controller.
  3. Add one alarm controller.
    .
    Please select the correct Model No according to the installed alarm controller. If not connected to any alarm controller, set the Model No to Built-In IO.
  4. Click OK to confirm and save settings.

Input Point Setup

  1. Open Input Point. Go to Server Admin › System Device Setup › Input Point.
  2. Add input point according to the connected input at the controller board.

    FieldDescription
    Code and DescriptionFill in the Code and Description
    Alarm ControllerSelect Alarm Controller
    Point NoSet the Input Point - Which Input Number (IN) the input is connected to.
    • Example: If Input is connected to IN2, set the Point No to 1.
    • The Input Point No start from 0 until 15.
    LED Point AssociationSet the LED Point Association
    PrioritySet the priority of the alarm trigger
  3. Please leave the Event Trigger Arm and Disarm blank. 
  4. Click OK to confirm and save settings.
    Input/ output triggering for XP-SNET/ XP-CPROA, see small How to configure Instruction Control for Input to trigger Output?

  1. Open Send Door Settings. Go to Device Comm › Send Door Setting.
  2. Download the Alarm Controller and Inputs settings to the controller.


  3. Finished.
    To configure Input, see small How to configure Output?
Attachments
snet-manual-v3.1.pdf 2.9 Mb Download File
Custom Fields
  • Summary: This article contains the steps to configure the Input.
  • Search Tags: input, input setup, how to setup input, input configuration, input point