How to reset the XP-SNET controller to factory default setting? (Coldstart)
Author: Microengine Views: 18349 Created: 19-03-2015 05:58 PM 0 Rating/ Voters

This article contains steps to reset (Coldstart) the XP-SNET controller to default setting.

Applies To:

  • XP-SNET    
 Problem
 

› Forgot Server IP Address.
 How to reset the setting to default factory settings?   

         
 Symptoms
 
 Unable to enter to Web Diagnostic.

         
 Cause (optional)
 
 Incorrect Server IP Address was set in Web Diagnostic.

         
 Resolution Summary
 

 Perform Coldstart to reset back the setting to default.

         
 Resolution
 

Performing Coldstart will reset the XP-SNET controller to manufacturer settings. To perform a Coldstart, please follow the steps below:

Warning! Coldstart will reset all setting to default factory settings. Skip this step if you did not wish to reset the controller.

To perform Coldstart during power up: 

  1. Press on Coldstart button for 5 seconds.

To perform Coldstart during idle state:

  1. Press on Coldstart button for 5 seconds.
  2. Release Reset button while holding down Coldstart button until a short beep.
  3. During reset:
    • Red LED will turn ON.
    • Yellow LED will turn OFF.
    • Green LED will be blinking.
  4. When Coldstart complete, Red LED will turn OFF while Yellow LED will start blinking.

Custom Fields
  • Summary: This article contains steps to reset (Coldstart) the XP-SNET controller to default setting.
  • Search Tags: coldstart xp-snet, reset to default setting, clear all records