› After configure floor accessibility for XP-SNET for lift controller the floor accessibility does not work, the user can still access all floor.
› User still can access the floor which have given no access right.
› Incorrect wiring connection at relay board.
› Incorrect Floor Relay Setup at xPortal Server.
› Incorrect Floor Accessibility Setup at xPortal Client.
Resolution 1:
› Make sure your wiring connection from controller to relay board is correct.
› Make sure all relays are correctly connected.
Resolution 2:
› Please make sure the server setup are correctly configured.
Resolution 3:
› Please make sure the client setup are correctly configured.
Please perform steps below to solve the issue:
Resolution 1:
- Please check your wiring connection from XP-SNET controller to the SNET-E32R extension board is correct.
- Refer to Figure 1 below.
Figure 1
» For high resolution image, please download the attached wiring diagram at the end of this article.
- This is an example of wiring connection diagram for 1 Lift Controller connected to 128 floors.
(Must connected with 4 units of SNET-E32R extension board) - 1 SNET-E32R = Support 32 floors.
- 1 XP-SNET Lift controller = Support 128 floors (Maximum can connected to 4 units of SNET-E32R).
- Make sure CON35/ 36/ 37 at XP-SNET controller is correctly connected to CON34/ 35 at SNET-E32R.
Resolution 2:
- Make sure the floor relay setup is correctly configured at xPortal Server software.
- See AA-00300 to configure the setup at xPortal Server.
» If you connect more than 1 SNET-E32R board, make sure you set the board address and relay number correctly.
SNET-E32R Board Address |
Relay Number Range |
0 |
0-31 |
1 |
32-63 |
2 |
64-95 |
3 |
96-127
|
Resolution 3:
- Make sure the floor accessibility setup is correctly configured at xPortal Client software.
- See AA-00301 to configure the setup at xPortal Client.